#11566: ZoneHVAC:HybridUnitaryHVAC - Return Air constraints not referenced#11576

Draft
kevin-moos wants to merge 3 commits intoNatLabRockies:developfrom
bigladder:HybridUnitaryHVAC-fix-return-air-constraints
Draft

#11566: ZoneHVAC:HybridUnitaryHVAC - Return Air constraints not referenced#11576
kevin-moos wants to merge 3 commits intoNatLabRockies:developfrom
bigladder:HybridUnitaryHVAC-fix-return-air-constraints

Conversation

@kevin-moos
Copy link
Copy Markdown
Contributor

Pull request overview

Description of the purpose of this PR

Add logic to check Return Air constraints for temperature, humidity ratio, and relative humidity. Add bools to track whether Min/Max Return Temp constraints were left blank in the IDF. Update logic to ignore these constraints when left blank.

Pull Request Author

  • Title of PR should be user-synopsis style (clearly understandable in a standalone changelog context)
  • Label the PR with at least one of: Defect, Refactoring, NewFeature, Performance, and/or DoNoPublish
  • Pull requests that impact EnergyPlus code must also include unit tests to cover enhancement or defect repair
  • Author should provide a "walkthrough" of relevant code changes using a GitHub code review comment process
  • If any diffs are expected, author must demonstrate they are justified using plots and descriptions
  • If changes fix a defect, the fix should be demonstrated in plots and descriptions
  • If any defect files are updated to a more recent version, upload new versions here or on DevSupport
  • If IDD requires transition, transition source, rules, ExpandObjects, and IDFs must be updated, and add IDDChange label
  • If structural output changes, add to output rules file and add OutputChange label
  • If adding/removing any LaTeX docs or figures, update that document's CMakeLists file dependencies
  • If adding/removing any output files (e.g., eplustbl.*)
    • Update ..\scripts\Epl-run.bat
    • Update ..\scripts\RunEPlus.bat
    • Update ..\src\EPLaunch\ MainModule.bas, epl-ui.frm, and epl.vbp (VersionComments)
    • Update ...github\workflows\energyplus.py

Reviewer

  • Perform a Code Review on GitHub
  • If branch is behind develop, merge develop and build locally to check for side effects of the merge
  • If defect, verify by running develop branch and reproducing defect, then running PR and reproducing fix
  • If feature, test running new feature, try creative ways to break it
  • CI status: all green or justified
  • Check that performance is not impacted (CI Linux results include performance check)
  • Run Unit Test(s) locally
  • Check any new function arguments for performance impacts
  • Verify IDF naming conventions and styles, memos and notes and defaults
  • If new idf included, locally check the err file and other outputs

OAHRConstraintmet = true;
}
bool RATempConstraintMet = (Minimum_Return_Air_Temperature_Blank || Tra >= Minimum_Return_Air_Temperature) &&
(Minimum_Return_Air_Temperature_Blank || Tra <= Maximum_Return_Air_Temperature);
Copy link
Copy Markdown
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Should the 2nd Minimum_RA_Temp_Blank be Max?

Copy link
Copy Markdown
Contributor Author

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Yes, thanks for catching that one!

if (Tosa >= Minimum_Outdoor_Air_Temperature && Tosa <= Maximum_Outdoor_Air_Temperature) {
OATempConstraintmet = true;
}
bool OATempConstraintMet = (Tosa >= Minimum_Outdoor_Air_Temperature && Tosa <= Maximum_Outdoor_Air_Temperature);
Copy link
Copy Markdown
Collaborator

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Doesn't OAT have the same issue with a blank Min/Max OAT? I also don't see how the other default limits are applied? e.g., Min/Max humrat of 0.0 and 0.1 or RH of 0% and 100%, where do these get set? All these CMode::Initialize functions just return true, so how do any of the warnings following these function calls get executed? i.e., lines 610, 618 and 628.

@mitchute mitchute added Defect Includes code to repair a defect in EnergyPlus labels May 4, 2026
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Labels

Defect Includes code to repair a defect in EnergyPlus

Projects

None yet

Development

Successfully merging this pull request may close these issues.

ZoneHVAC:HybridUnitaryHVAC - Return Air constraints not referenced

4 participants